When a Siemens SINAMICS V20 drive stops the motor and shows a code starting with F, it has tripped on a fault. A code starting with A is an alarm: a warning that the drive keeps running through, but that often turns into a fault if nobody acts on it.
This guide lists the V20 fault and alarm codes, what each one means, and the parameters to check. It is based on the SINAMICS V20 Operating Instructions, edition 01/2018 (A5E34559884-009), chapter 9 “Faults and alarms”. Newer firmware can add codes, so for an unfamiliar code check the manual edition that matches your drive.
Before you start
- Safety first: switch off and isolate the supply before touching the drive, motor or cables. The DC link stays charged for several minutes after power-off; wait for the time stated on the drive before working inside.
- Note the code before resetting it. The last fault codes are stored in r0947 and active alarms in r2110. Many faults also store a fault value in r0949 that tells you the exact cause; the tables below mention it where it helps.
- Faults must be acknowledged after the cause is fixed, from the operator panel (BOP) or externally if the drive has been set up for that. A few faults can only be cleared by switching the power off and on. Alarms cannot be acknowledged; they clear themselves once the condition is gone.
- Check the motor data first. Many trips come from motor data that does not match the motor. The nameplate data is entered in P0304–P0311 (voltage, current, power, cos φ, frequency and speed), and motor data identification is run with P1900.
SINAMICS V20 fault codes
| Code | Fault | Cause | What to check |
|---|---|---|---|
| F1 | Overcurrent | Motor power (P0307) does not match the drive power (r0206); short circuit in the motor cable; earth fault. | Motor power must match the drive; cable length within limits; no short circuit or earth fault in cable or motor; motor parameters and stator resistance (P0350) correct; motor not jammed or overloaded. Increase the ramp-up time (P1120) and reduce the starting boost (P1312). |
| F2 | Overvoltage | Supply voltage too high, or the motor is regenerating (fast ramp-down, or the motor is driven by the load). | Supply voltage (P0210) within the rating plate limits; ramp-down time (P1121) long enough for the load inertia; braking power within limits; Vdc controller enabled (P1240). With high inertia, use longer ramps or a braking resistor. |
| F3 | Undervoltage | Supply failure, or a shock load outside the specified limits. | Check the supply voltage. |
| F4 | Inverter overtemperature | Drive overloaded, poor ventilation, pulse frequency too high, ambient too hot, fan not working. | Load and duty cycle; motor power vs drive power; pulse frequency at its default; ambient temperature; the fan must turn when the drive runs. |
| F5 | Inverter I²t | Drive overloaded, load cycle too demanding, or motor power (P0307) above the drive’s capability (r0206). | Load cycle within limits; motor power vs drive power. F5 cannot be cleared until the drive utilisation (r0036) falls below the I²t warning level (P0294). |
| F6 | Chip temperature rise exceeds critical levels | Starting load too high, load step too high, ramp-up too fast. | Increase the ramp-up time (P1120); motor power vs drive power. Setting P0290 = 0 or 2 helps prevent F6. |
| F11 | Motor overtemperature | Motor overloaded. Can also occur with small motors running below 15 Hz even when the motor is not actually hot. | Load and load steps; motor overtemperature settings (P0626–P0628) and warning level (P0604). For small motors at low speed: if the motor current is within its nameplate rating and the motor temperature is normal, set P0335 = 1. |
| F12 | Inverter temperature signal lost | Wire break in the drive’s heat sink temperature sensor. | Internal fault: contact service. |
| F20 | DC ripple too high | Usually loss of one supply phase. | Check the supply wiring, fuses and terminals. |
| F35 | Maximum number of auto-restart attempts exceeded | Automatic restart tried more times than set in P1211. | Find and fix the fault that caused the restarts. Automatic restart is configured in P1210. |
| F41 | Motor data identification failure | r0949 = 0: no load connected; 1: current limit reached; 2: identified stator resistance out of range; 30: current controller at voltage limit; 40: inconsistent data. | Is the motor connected? Are the motor data in P0304–P0311 correct? Is the motor wired in star or delta as required? |
| F51 | Parameter EEPROM fault | Read or write failure in the parameter memory. Can be caused by the memory being full after many parameter changes (r0949 = 1). | Power-cycle. If it remains, factory reset and parameterise again, or set some parameters back to default if the memory is full. Otherwise replace the drive. |
| F52 | Inverter software fault | Read failure or invalid data for the inverter information. | Power-cycle; if it remains, contact service or replace the drive. |
| F60 | ASIC timeout | Internal communication failure. If sporadic, often caused by EMC (electrical noise). | Check the drive; improve EMC (screened cables, correct earthing) and use an EMC filter. |
| F61–F64 | SD card parameter cloning faults | Card missing or unreadable (F61), clone file invalid (F62) or from an incompatible drive type (F63), or automatic clone attempted at start-up with no valid file (F64). | Use a FAT16/FAT32 card with the correct file in /USER/SINAMICS/DATA. If no automatic clone is wanted, remove the card, set P8458 = 0 and power-cycle. These faults clear only with a power-cycle. |
| F70 | I/O Extension Module communication fault | Communication with the I/O Extension Module lost. | Reconnect the module and check it, then acknowledge. Replace the module if the fault remains. |
| F71 / F72 | USS / USS-Modbus setpoint fault | No setpoint received from the USS or Modbus master within the telegram off time. | Check the master, the communication cable and the telegram off-time setting. |
| F80 | Signal lost on analog input | Broken wire, or signal out of limits. | Check the analog input wiring and the signal source. |
| F85 | External fault | External fault triggered through a command input (control word 2, bit 13), for example a thermistor relay or interlock. | Check the source set in P2106 and the external device; disable the terminal input for the fault trigger if it is not used. |
| F100 / F101 | Watchdog reset / Stack overflow | Software error or processor failure. | Contact service or replace the drive. |
| F221 / F222 | PID feedback below minimum / above maximum | PID feedback outside the limits in P2268 (minimum) or P2267 (maximum). | Check the feedback sensor and wiring; adjust the limit or the feedback gain. |
| F350 | Configuration vector for the inverter failed | Hardware does not match the drive configuration; r0949 = 13 means the wrong power module is fitted. | Make sure the right power module is fitted; otherwise contact service. Clears only with a power-cycle. |
| F395 | Acceptance test / confirmation pending | After a start-up clone (for example from an SD card) or a faulty EEPROM read, the parameter set may not match the application. | Check the current parameter set, then confirm it by clearing the fault. |
| F410 | Cavitation protection failure | Conditions for pump cavitation (not enough fluid flow). | If there is no cavitation, reduce the threshold P2361 or increase the protection delay. Check the sensor feedback. |
| F452 | Load monitoring trip | Load indicates a broken belt or mechanical fault (r0949 = 0: low torque/speed; 1: high). | Check the drive train for breakage, seizure or obstruction; lubricate. Check the load monitoring thresholds P2182–P2190 and delay P2192. |
SINAMICS V20 alarm codes
| Code | Alarm | Meaning and what to do |
|---|---|---|
| A501 | Current limit | Motor power does not match the drive, motor leads too long, or earth fault: see F1. Very small motors (120 W) on light load in FCC mode can also cause it; use V/f control for very small motors. |
| A502 | Overvoltage limit | Can occur during ramp-down when the Vdc controller is disabled (P1240 = 0). If it stays on permanently, check the supply voltage. |
| A503 | Undervoltage limit | Supply failure, or DC link voltage (r0026) below the limit. Check the supply voltage. |
| A504 | Inverter overtemperature | Heat sink or chip temperature warning level exceeded; the drive reduces pulse and/or output frequency depending on P0290. Temperatures are shown in r0037. Check ambient temperature, load and the fan. |
| A505 | Inverter I²t | Overload warning level exceeded. Check that the load cycle is within limits. |
| A506 | IGBT junction temperature rise | Overload warning. Check load steps and shock loads. |
| A507 | Inverter temperature signal lost | Heat sink temperature sensor signal lost. Contact service. |
| A511 | Motor overtemperature I²t | Motor overloaded or load steps too high. Check the warning threshold (P0604), motor ambient temperature (P0625) and nameplate data; run motor identification (P1900 = 2); check motor weight (P0344). |
| A535 | Braking resistor overload | Braking energy too high for the resistor. Reduce the braking energy or use a higher-rated resistor. |
| A541 | Motor data identification active | Identification (P1900) is selected or running. Normal during commissioning. |
| A910 | Vdc_max controller deactivated | Supply permanently too high, motor driven by the load, or very high inertia during ramp-down. Check the input voltage and load; a braking resistor may be needed. |
| A911 | Vdc_max controller active | The drive is extending the ramp-down to hold the DC link voltage down. Check the supply voltage and that the ramp-down time (P1121) suits the load inertia. |
| A912 | Vdc_min controller active | The drive uses the motor’s kinetic energy to ride through a short supply dip, which slows the motor. |
| A922 | No load applied to inverter | No motor load detected. Check that the motor is connected. |
| A923 | Both JOG left and JOG right requested | Do not request both JOG directions at once. |
| A930 / A952 | Cavitation protection / Load monitoring warning | Early warnings of F410 and F452. |
The five most common causes we find on site
- Ramps that are too short. Fans and loaded conveyors with high inertia need longer acceleration (P1120) and deceleration (P1121) times. Short ramps cause F1 or F6 on start and F2 on stop.
- Wrong motor data. Enter the nameplate data in P0304–P0311 and run motor identification (P1900).
- Heat in the panel. Drives in a closed, unventilated panel trip on F4 and A504, especially in summer. Check fans, filters and clearances, and keep the pulse frequency (P1800) at its default.
- Supply problems. Loose terminals, a blown fuse in one phase or long, thin cables cause F3 and F20.
- Cable and motor insulation. Damaged or wet cables and old windings cause F1 earth faults. Test insulation with the drive disconnected.
For the wider picture, see our guide to troubleshooting common VFD motor problems.
When to call for help
Call us if a fault keeps returning after you have checked the points above, if the drive shows internal faults such as F12, F52, F60 or F100, or if you need to resize the drive for the load. We supply the full SINAMICS drive range and support V20 drives across North India. TMG Engineers & Associates, an NMA Group company, is a certified Siemens Solution Partner for Drives & Motion.
Frequently asked questions
What is the difference between a fault and an alarm on the V20?
A fault (F) stops the motor and must be acknowledged. An alarm (A) is a warning: the drive keeps running, and the alarm clears itself once the cause is gone.
How do I find the last faults on a V20?
The recent fault codes are stored in parameter r0947, and r0949 holds the fault value with more detail about the cause.
Why does my V20 trip on F1 only when starting?
Usually because the ramp-up time (P1120) is too short for the load or the starting boost (P1312) is too high. Also check that the motor power matches the drive and the motor data are correct.
Why does my V20 trip on F2 when stopping?
The motor is regenerating energy faster than the drive can absorb it. Increase the ramp-down time (P1121), make sure the Vdc controller is enabled (P1240), or add a braking resistor for high-inertia loads.
Why won’t F5 reset?
F5 can only be cleared once the drive’s overload utilisation (r0036) drops below the I²t warning level (P0294). Let the drive cool down, then acknowledge.
Contact NMA Group for V20 support, spares or a replacement drive.